TESTING & CERTIFYING THE SAFETY OF STATIC PROTECTIVE FIBC
TESTING & CERTIFYING THE SAFETY OF STATIC PROTECTIVE FIBC by Dr. Paul Holdstock, Texene LLC.
Industry is now familiar with the different types of static
protective FIBC known as Type C and Type D. Perhaps less well know is
how the different types are tested and certified for safe use in
hazardous flammable environments. Type C FIBC, which rely on a
conductive path to ground to safely dissipate electrostatic charge can
be tested by measuring electrical resistance. However, until recently
manufacturers had their own ways of doing this, some of which were not
entirely suitable. For example, one commonly used method involved
placing the FIBC flat on a table and measuring the resistance of the
fabric surface using an electrode arrangement of a cylindrical
electrode surrounded by a ring electrode. Whilst this is a standard
arrangement for many textile applications, it is of limited use for
measurements on FIBC. The electrode arrangement only measures across a
small area of fabric, and so it can only be used to confirm that small
areas of fabric are sufficiently conductive. Such an arrangement cannot
determine the integrity of ground connections throughout the entire
FIBC. Even if measurements are made with widely spaced electrodes, i.e.
point-to-point resistance measurements, the fact that the FIBC is lying
flat on a table may cause connections that would not be there when the
FIBC is opened out and filled with product.
Testing of Type D FIBC was even more irregular. Unlike Type C FIBC,
where the mechanism of charge dissipation is directly related to a
single, measurable physical quantity, i.e. resistance, no such
relationship exists for Type D FIBC. Charge dissipation in Type D FIBC
is a result of a process that is dependent on geometrical and
electrical parameters. Consequently, a variety of measurements were
used by test laboratories in an attempt to determine safety
performance. Measurements such as surface potential, charge decay time,
charge transfer, etc. were all used. The problem was that none of these
measurements could really answer the fundamental question of whether or
not the ungrounded FIBC could be used in flammable environments without
producing incendiary discharges. It was, therefore, almost impossible
for end users to make a meaningful decision about the safety of Type D
FIBC, or indeed how one FIBC compared to others.
Ignition testing has become the preferred test procedure for Type D
FIBC. The principle behind ignition testing is to charge an FIBC,
present a flammable atmosphere and try to provoke an electrostatic
discharge. Several test laboratories offer ignition testing, but there
are variations in their test parameters and conditions. An FIBC that
passed in one laboratory may have failed in another.
IEC 61340-4-4:2005 - The Standard for Testing Static Protective FIBC
In 1999, the International Electrotechnical Commission (IEC)
Technical Committee on Electrostatics (TC 101) launched a project to
standardise test procedures for static protective FIBC. The project
culminated in the publication in 2005 of the International Standard IEC
61340-4-4:2005 Electrostatics - Part 4-4: Standard test methods for
specific applications - Electrostatic classification of flexible
intermediate bulk containers (FIBC). This important International
Standard specifies test procedures for FIBC that must be grounded (Type
C) and those for which ground connection is not necessary (Type D). The
test procedure specified for Type C FIBC is based on resistance
measurements, and ignition testing is specified for Type D FIBC. In
addition, to these tests, the fabric used in the construction of both
Type C and Type D FIBC must be tested to determine breakdown voltage.
Breakdown voltage of below 6 kV ensures that FIBC cannot generate
highly energetic propagating brush discharges.
Testing for Type C
The resistance measurement procedure for Type C FIBC requires the
FIBC to be suspended from its lifting loops as it would be in normal
operation. Measurements are made between conducting yarns and each of
the designated ground bonding points. Testing in this way ensures not
only that the fabric is sufficiently conducting, but also that there is
electrical continuity throughout the entire FIBC. Measurements are made
at both low humidity (20 ± 5 % RH) and high humidity (60 ± 10 % RH).
Type C FIBC can only be qualified under IEC 61340-4-4:2005 if all the
measured resistance values are less than 10^8, and the breakdown
voltage is less than 6 kV.
Testing for Type D
The two main parameters that define the challenge of ignition testing
is the charging current, i.e. how much charge is delivered to the FIBC
under test, and the minimum ignition energy (MIE) of the challenge gas,
i.e. how easy it is to ignite. Prior to the introduction of IEC
61340-4-4:2005, charging currents used by some test laboratories were
quite low, often less than 1 µA (microamp). The reason behind this
choice of charging current was that it was sufficient to cause ignition
from a plain non-static protective FIBC (i.e. Type A). However, testing
with such low charging currents can only show that an FIBC is somewhat
better than a Type A FIBC. In order to be qualified as safe, FIBC must
be challenged with a charging current that is representative of the
worst case likely to be found in practice. Data from end users confirm
that 3 µA is a better representation of the highest charging current
found in FIBC handling operations. A similar argument was used to
define the MIE of the challenge gas. The most easily ignitable solvent
vapour likely to be used in FIBC handling operations is methanol heated
above ambient temperature, which has a MIE of about 0.14 mJ. This is
the value specified for ignition testing in IEC 61340-4-4:2005,
although it is achieved by using a 5.4% mixture of ethylene in air. The
gas mixture, flow rate and means of control are all specified in the
IEC standard to ensure the accuracy, reproducibility of test results,
and simulation of the range of environments to which the FIBC is
exposed.
The procedure for ignition testing is to fill the FIBC under test
with polypropylene pellets of a specified size range into which charge
is injected at a rate of -3 µA. Negative polarity is used because
research data predicts that electrostatic discharges from negatively
charged materials are more likely to cause ignition than those from
positively charged surfaces. For Type D FIBC, the testing is carried
out with the FIBC completely isolated from ground. Charging in this way
is a good simulation of actual FIBC handling operations. As the FIBC is
being filled with charged pellets, a gas probe is brought up to the
side of the FIBC. The gas probe contains a grounded, spherical
electrode surrounded by a shroud that directs a flow of flammable gas
in front of the electrode. Any electrostatic discharge that is
generated when the probe approaches the FIBC will pass through the
localised flammable atmosphere and if it contains sufficient energy it
will cause the ignition. If the FIBC under test is a correctly designed
Type D, then no ignition will occur. However, to prove this the gas
probe must be brought up to different areas covering all parts of the
FIBC in multiple approaches. IEC 61340-4-4:2005 specifies that at least
50 approaches must be made to each side of the FIBC, and at least 10
additional approaches to all other panels, spouts and other accessories
on the FIBC. As with resistance measurements, ignition testing must be
done at both low and high humidity. It is also a requirement of the IEC
standard for ignition testing to be carried out on the largest and
smallest size of FIBC of a particular design. On a typical FIBC, about
400 to 500 gas probe approaches must be made. If any one of these
approaches results in an ignition then the FIBC is considered to have
failed. Type D FIBC can only be qualified under IEC 61340-4-4:2005 if
no ignition occurs during ignition testing, and the breakdown voltage
is less than 6 kV.
Labelling
In addition to specifying test procedures and performance
requirements, IEC 61340-4-4:2005 also specifies how FIBC that have been
qualified in accordance with the standard should be labelled. The
minimum information required on the label for Type C FIBC is:
The minimum information required on the label for Type D FIBC is:
Qualification
Only FIBC that have been qualified exactly in accordance with the
procedures specified in IEC 61340-4-4:2005 can legitimately be labelled
as such. FIBC that have not been tested in strict accordance with the
IEC standard cannot be labelled in this way. Qualification to IEC
61340-4-4:2005 must be supported by test reports that fulfil all the
requirements of the standard. Older test reports, even if the test
procedures are similar to those specified in the standard, cannot be
legitimately used to support qualification to IEC 61340-4-4:2005. This
is because older test procedures may not involve the rigorous control
and calibration requirements specified in the IEC standard, and may not
produce equivalent results. It is, therefore, important when checking
test reports to ensure that all the information is reported in
accordance with the IEC standard. That includes specific details of the
test parameters and conditions, which for ignition testing should
include, temperature and relative humidity, filling rate, charging
current, gas composition, gas flow rate, MIE and number and location of
gas probe approaches. A summary of the test parameters and conditions
specified in IEC 61340-4-4:2005 is shown in the table below:
Test Parameter Value
Temperature / Humidity a) 23 ± 2 °C and 20 ± 5 %RH
b) 23 ± 2 °C and 60 ± 10 %RH
Filling rate 1.1 0.1 kg/s
Charging current 3.0 ± 0.1 µA (negative polarity)
Gas composition 5.4 ± 0.1 % ethylene (balance air)
Gas flow rate 0.21 ± 0.04 l/s
Minimum ignition energy 0.14 ± 0.01 mJ
Number of gas probe approaches At least 200 at each humidity level
Non-Standard FIBC
There exists on the market today FIBC that are sold as Type D FIBC
but do not comply with the requirements of IEC 61340-4-4:2005. Some of
these FIBC existed before the standard was published and their
manufacturers have not improved their designs in order to meet the
standard. Others have been designed in an attempt to get round the
standard. The purpose of any standard is to set minimum acceptable
levels of performance without placing an undue burden on manufacturers.
In the case of IEC 61340-4-4:2005, the purpose is to establish a
minimum level of safety to ensure that FIBC tested using the specified
methods and meeting the specified performance requirements are
qualified as safe for use in a broad range of industries. The test
methods and associated limit values were established by an
international committee of experts encompassing FIBC manufacturers,
test laboratories, process safety engineers and FIBC end users. It is
fair to say that IEC 61340-4-4:2005 represents the current state of
knowledge as to what constitutes a safe static protective FIBC. A great
deal of caution, therefore, needs to be exercised when considering FIBC
that do not comply with the IEC standard.
Some FIBC manufacturers have tried to invent their own classification
and label their FIBC as D+, Dplus, CD, etc. They make claims to the
effect that their FIBC are Type C that do not need to be grounded, or
are groundable Type D. For a start, none of these designations are
recognised in any national or international standard. The requirements
for Type C FIBC are very clearly defined in IEC 61340-4-4:2005. For a
Type C FIBC to meet the required safety standard, the resistance to
ground must be less than 10^8 and the FIBC must be grounded during
normal operations. If the resistance to ground is greater than 10^8,
the FIBC cannot be legitimately described as Type C. If a Type C FIBC
is used without a proper ground connection, incendiary sparks will be
produced. The requirements for Type D FIBC are also clearly defined in
the IEC; they must pass the specified ignition test without being
grounded. If an FIBC needs to be grounded in order to pass the IEC
standard ignition test, then it cannot be legitimately described as
Type D. Logically, if a FIBC cannot meet the basic safety requirements
of Type D, it is nonsense to describe it as D+. The use of non-standard
classification on FIBC is a transparent marketing gimmick for FIBC that
do not comply with recognised safety standards.
How to Identify FIBC Qualified to IEC 61340-4-4:2005
There are three components to establishing whether or not an FIBC has
been qualified according to IEC 61340-4-4:2005:-
1) A label on the FIBC containing at least the information specified in IEC 61340-4-4:2005;
2) A test report showing results of breakdown voltage measurements
(Type C & Type D), and resistance measurements (Type C) or
ignition testing (Type D);
3) A test certificate confirming that the FIBC meets all the
requirements of IEC 61340-4-4:2005. This may be a separate certificate
or incorporated as part of the test report.
A valid test report must contain details of all the relevant test
parameters and conditions specified in IEC 61340-4-4:2005 and a full
description of the FIBC under test. If a separate test certificate is
provided, the test report on which it is based must be available for
inspection. There are examples of test certificates that imply testing
was done according to IEC 61340-4-4:2005 but when test reports are
inspected it is clear that there a significant deviations from
specified procedures that render the test report invalid as a means of
supporting qualification to IEC 61340-4-4:2005.
Testing & Certifying CROHMIQ® Static Protective Type D FIBC
Texene LLC is the only company in the FIBC industry to own and
operate its own state-of-the-art FIBC testing facility that is designed
and built to meet the exact requirements of IEC 61340-4-4:2005. The
testing facility is used to qualify FIBC made from CROHMIQ® Static
Protective FIBC Fabrics, for quality control testing, and to support
the Texene Continuous Safety Certification Programme™ (CSC). The CSC
Programme is a unique, complimentary service provided by Texene to
users of CROHMIQ® Static Protective Type D FIBC. The first stage of CSC
is the initial safety qualification. Each design of CROHMIQ® FIBC is
tested according to IEC 61340-4-4:2005 prior to despatch of the first
shipment to the customer. Initial qualification is achieved by testing
3 samples of each FIBC design; each one must pass. The customer is
provided with a full test report and a summary test certificate. The
second stage of CSC is the continuous re-qualification of CROHMIQ®
FIBC. At regular intervals agreed with the customer, e.g. every six
months, or every 10,000 FIBC delivered, the customer sends one sample
of each CROHMIQ® FIBC design to Texene for re-qualification. Testing is
again conducted according to IEC 61340-4-4:2005 and the customer is
provided with a summary certificate and full test report for each
re-qualification test.
CROHMIQ® FIBC are used throughout the world by major companies as an
essential part of their regulation of electrostatic hazards. Thanks to
their outstanding safety record, CROHMIQ® FIBC are widely acknowledged
as the safest and most cost effective solution for controlling static
electricity in FIBC handling operations.
For more information about CROHMIQ® FIBC fabrics, visit www.crohmiq.com.
TEXENE LLC is a leading manufacturer of technical textiles focused on delivering precision engineered, safety performance products worldwide.













