NEW DEVELOPMENTS IN SAFETY STANDARDS FOR STATIC PROTECTIVE FIBC

Many applications for FIBC require the use of electrostatic protected bags to prevent the ignition of flammable powders that may be transported in them or of flammable vapours that may be present when they are being discharged. For many years, industry has used a classification scheme based on four types of FIBC distinguished according to their area of use and method of protection. Type A are plain FIBC without any means of electrostatic protection. They are intended for use when no flammable powder or vapour is present. Type B are similar to Type A, but they must be constructed from materials that have an electrical breakdown strength of less than 4 kilovolts. They are intended for use where flammable powders may be present, but where there are no flammable solvents or vapours. Dry powders with minimum ignition energy (MIE) of greater than 3 millijoule may only be ignited by very energetic discharges called propagating brush discharges (PBD). Based on work by Maurer et al , thin films with breakdown strengths below 4 kilovolts did not produce PBD. These results have been applied to FIBC materials, hence the requirement for Type B.

Sensitive powders

When more sensitive powders, or flammable gases and vapours are present, additional electrostatic protection is required. For such applications Type C or Type D FIBC are required. Type C are fully conductive bags, or bags made from fabric containing an interconnected grid of conductive yarns or tapes. To achieve full electrostatic protection Type C bags must always be connected to earth when used in the presence of a flammable atmosphere. Indeed, if a Type C bag were to become isolated from earth, it not only fails to provide protection, it adds to the danger because the isolated conductors can generate high energy spark discharges easily capable of igniting a flammable atmosphere. Type D FIBC were pioneered by LINQ Industrial Fabrics Inc in response to major industrial users that required a greater degree of safety than could be offered by Type C. By their very nature as transportable containers, FIBC cannot always be earthed. Human intervention is required to re-establish proper earth connection whenever a Type C bag is filled or emptied. Human error is inevitable and the consequences can be disastrous as evidenced by explosion incidences contained in Britton's paper of 1993 . Type D bags eliminate the danger from human error by providing continuous electrostatic protection without the need of an earth connection. LINQ introduced Crohmiq blue™ as the first effective material to provide continuous electrostatic protection for FIBC without earthing, and the Type D FIBC was born. During the past decade Crohmiq blue™ has established a faultless safety record with over 8 million bags used around the world without incident. Over 2 million of these bags were bags reused after wet or dry process refurbishing. It is fair to say that Crohmiq blue™ has become synonymous with Type D.

Latest technology

Until recently, the type classification scheme,

March/April 2004 Industrial Bulk & Processing 35

March/April 2004

Bulk Product Inside FIBC (MIE of Powder) Substances in Surrounding Atmosphere
No Flammable Atmosphere Flammable Dust Atmosphere Explosive Gas/Vapour (Group IIA or IIB
Greater than 1000 mJ Type A, B, C or D Type B, C or D Type C or D
3 mJ to 1000 mJ Type B, C or D Type B, C or D Type C or D
Less than 3 mJ Type C or D Type C or D Type C or D

Table 1. Guidance on when different types of FIBC should be used (from CLC TR 50404:2003)

although widely known, had not been formalised in any kind of standard. Codes of practice such as BS 5958 and ZH1/200 did include guidance on the use of FIBC, but they did not differentiate between FIBC with the type classification system, nor did they address the safe use of FIBC not connected to earth. As a consequence of the safety record established for Type D FIBC by Crohmiq blue™, CENELEC has included Type D in the latest code of practice to be published in Europe: CLC TR 50404:2003 Electrostatics - Code of practice for the avoidance of hazards due to static electricity. For the first time, this code of practice establishes formal definitions for Types A, B, C and D and just as importantly gives users guidance on when and how to use each type. The guidance is summarised in Table 1. As the Table shows, for the most hazardous situations, when sensitive flammable powders may be present inside FIBC, or when sensitive dusts, gases or vapours are present outside FIBC, full electrostatic protection is required. In these situations safety can be achieved equally by using Type C or Type D. The code of practice emphasises the importance of providing a proper earth connection for Type C FIBC whenever they are filled or emptied, and that electrical continuity between all conductive elements within the bag shall be maintained by suitable design requirements. The resistance between any and all conductive elements shall be less than 10^8. There are no special design requirements for Type D. However, according to CLC TR 50404:2003 a Type D FIBC must be qualified as safe for use in a flammable atmosphere by demonstrating that it does not produce incendiary discharges. The International Electrotechnical Commission (IEC) is currently developing an International Standard for evaluating the electrostatic protection of FIBC intended for use in flammable atmospheres. For FIBC that are required to be earthed (i.e. Type C), evaluation is in the form of a simple resistance measurement to ensure electrical continuity throughout the bag and to its earth bonding point. There is no single measurable parameter for FIBC not required to be earthed

(i.e. Type D). Instead the draft IEC standard employs a test procedure based on the use of a gas probe. A gas probe is a device, which streams a flammable gas mixture around an earthed spherical electrode. When the probe is brought up to an electrostatically charged surface, the earthed sphere may initiate a spark or brush discharge through the flammable gas mixture (see Figure 1). To be qualified as safe, any spark or brush discharge produced from the FIBC surface must not ignite the flammable atmosphere when charged under conditions expected during normal operation.

Thorough testing is required

The FIBC under test must be charged in a way that accurately simulates how it is charged in practice, both in terms of the rate of charging and the distribution of the charge. In use, FIBC are charged as a result of the inflow and outflow of charged powder. This is simulated in the IEC method by the use of polypropylene pellets. The pellets will naturally become charged through their interaction with transport pipes and chutes, a process known as tribocharging. However, the nature of the testing demands that the rate of charging should be representative of the worst case likely to be found in practice. For this reason, the natural pellet charging is enhanced by the injection of charge from a high voltage corona. As one might expect, such testing is not just performed once. To be certain that an FIBC will not produce incendiary discharges, at least 200 approaches with the gas probe must be made encompassing all components of the FIBC. Furthermore, the test conditions must be as severe, or more severe than may be expected in practice. The severity of the test is determined by

36 Industrial Bulk & Processing March/April 2004

March/April 2004

Charging currents vary according to the process involved and at worst will be in the region of 1 to 3 mA. As a minimum safety requirement, Type D FIBC must be tested at least under these conditions. Any FIBC not able to complete this test procedure, under conditions of realistic severity, without producing a single ignition cannot be qualified as Type

D. In addition to pioneering Type D technology, LINQ Industrial Fabrics has played an active role in developing appropriate test methods. The test facility at LINQ's South Carolina headquarters is fully compliant with the draft International Standard and LINQ's technical experts are participating members of the joint IEC/ISO Working Group.

International standardisation

International standardisation is of vital importance to any industry. To quote from IEC's mission statement: "The IEC's multilateral conformity assessment schemes, based on its international standards, are truly global in concept and practice, reducing trade barriers caused by different certification criteria in various countries and helping industry to open up new markets. Removing the significant delays and costs of multiple testing and approval allows industry to be faster and cheaper to market with its products." With the publication of CLC TR 50404 in 2003 and the development of the IEC testing standard, industry will have a formalised assessment scheme that ensures the electrostatic safety of FIBC and will provide guidance on the selection and safe use of FIBC for different applications.

This article was written by: Dr Paul Holdstock Linq Industrial Fabrics Tel: +1 843 875 8119 Fax: +1 843 875 8237 Web: www.crohmiq.com

Are you using flexible intermediate bulk containers?

TEXENE LLC, Textile Technologies of the 21st Century
Textile Technologies of the 21st Century


TEXENE LLC is a leading manufacturer of technical textiles focused on delivering precision engineered, safety performance products worldwide.

ARTICLES ON ELECTROSTATICS

STATIC HAZARDS USING FLEXIBLE INTERMEDIATE BULK CONTAINERS FOR POWDER HANDLING
In the early 1990's, Dr Laurence G. Britton, a highly respected process safety engineer with Union Carbide Corp. (later Dow Corp.), conducted a study of fire and explosion incidents that occurred when FIBC were ...

DANGERS OF COMBUSTIBLE DUST EXPLOSIONS, OSHA REGULATIONS, AND ANTISTATIC FIBC
Following three fatal dust explosions in 2003 alone, the US Chemical Safety & Hazard Investigation Board (CSB) launched a wide ranging study of industrial dust explosions.  This first issue of our Electrostatic Safety ...

CHOOSING SAFE STATIC CONTROL FIBC
The second issue of our Electrostatic Safety Review outlines the development of conductive Type C FIBC and the later development of CROHMIQ, the world's first truly effective Type D FIBC fabric, which provides ...

TESTING & CERTIFYING THE SAFETY OF STATIC PROTECTIVE FIBC
The third issue in our series of Electrostatic Safety Reviews describes the rigorous testing that is demanded by national and international standards such (IEC, CENELEC, NFPA, etc.) in order to prove the safety of ...

NEW DEVELOPMENTS IN SAFETY STANDARDS FOR STATIC PROTECTIVE FIBC
Companies that handle combustible powders in bulk bags, or empty products from bulk bags in environments where flammable solvents may be present rely on safe antistatic FIBC to prevent fires and explosions. Proving safety ...

CHEMICAL ACCIDENTS IN THE NEWS

Sep 2nd, 2010
Oil Spill Seen In Gulf Platform Explosion
An oil and gas platform in the Gulf of Mexico exploded on Thursday, setting off ...

Sep 1st, 2010
Residents displaced by propane leak allowed to move back home
GILBOA, N.Y. -- The remaining residents displaced by last week's propane leak in Gilboa ...

Aug 31st, 2010
Chlorine leak contained at central Iowa General Mills plant
Officials are looking for the source of a small chlorine leak at a General Mills ...

Aug 31st, 2010
Explosion at BSU scares students, injures worker
BOISE -- It was quite the scare on the Boise State campus Monday as a ...

Aug 30th, 2010
Gas leak forces evacuations in Calhoun
Atlanta Gas Company works to repair the 2" gas line that was busted in downtown Calhoun. (...

Aug 30th, 2010
MUST SEE: Hydrogen fuel explosion caught on tape
ROCHESTER, NY (CNN) - Newly released surveillance video may help investigators figure out what caused ...

Aug 30th, 2010
Evacuation order cancelled for chemical leak
People, evacuated from their homes after a chemical in North Baton Rouge, are now allowed ...

Aug 30th, 2010
Ammonia leak reported at Georgia poultry plant
ROCKMART, Ga. -- Authorities say an ammonia leak at a West Georgia poultry plant sent 23 ...

Aug 30th, 2010
Tesoro: Hydrogen Attack Caused Anacortes Blast
Tesoro Anacortes Refinery announced Friday what investigators determined was the likely cause of an April 2 ...

Aug 30th, 2010
Blaze Erupts At Scrap Yard In Aliquippa
ALIQUIPPA, Pa. -- Firefighters spent early Monday morning battling a blaze that broke out at ...

Aug 29th, 2010
Long Island Man Burned In Garage Explosion
BY ADRIAN CARRASQUILLO A Baldwin man and his son were working in their detached garage ...

Aug 29th, 2010
BRIDGEPORT BLAZE: Fire hits abandoned ammunition plant
Click to enlarge Firefighters with Ladder 11 battle a fire at the former Remington Arms plant, ...

Aug 29th, 2010
Chemical Spill Sickens Dozens in Vegas
CNN that a chemical spill in the pool area of the MGM Grand Hotel in ...

Aug 27th, 2010
Eleven Treated At Possible SF Wharf Hazmat Site
SAN FRANCISCO -- A possible hazardous materials incident at a recycling facility at Pier 96 in ...

Aug 27th, 2010
Pinhole leak reported at Valero hydrocracker in Benicia
BENICIA -- Valero Energy Corp. this week reported yet another vapor release at its Benicia ...

Aug 27th, 2010
Explosion near Rochester airport deemed an accident
A fiery explosion that shook the Greater Rochester International Airport and was heard across the ...

Aug 25th, 2010
1 injured in gas compressor station explosion
at 4:18 p.m. Last Modified: Wednesday, August 25, 2010 at 4:18 p.m. SHONGALOO, La. - An explosion ...

Aug 25th, 2010
Rockmart poultry plant leak caused by faulty seal; More than 20 sent to hospitals
Floyd Medical Center employee Katie Hastey helps a Rome Fire fighter change into protective gear ...

Aug 24th, 2010
Fire does minor damage at S.D. ethanol plant
CHANCELLOR (AP) — A spokesman for Sioux Falls-based ethanol producer Poet says a fire at a ...

Aug 24th, 2010
At least 120 sent to hospitals by ammonia leak at Ala. plant; 4 in intensive care
THEODORE, ALA. — An ammonia leak at a coastal Alabama chicken distribution plant sent more than 120 ...

Aug 23rd, 2010
Weekend ammonia leak at Cutler packing plant sent six to hospital; repairs must be made before business can reopen
Six workers at the Wawona Packing plant in Cutler suffered what are believed to be ...

Aug 23rd, 2010
Worker injured in explosion inside Bryan tire plant
A factory worker was hurt seriously early Monday during an explosion inside a Bryan tire ...

Aug 23rd, 2010
Chemical leak sets off factory's burglar alarm
A burglar alarm at Moore Metal Finishing on Silica Avenue in Sylvania Township apparently wasn't ...

Aug 22nd, 2010
Plant Explosion in Beatrice
A plant explosion in Beatrice sent two men to the hospital Sunday morning now the ...

Aug 22nd, 2010
Portland Asphalt Factory Fire
Several Area Fire Departments On Scene Of Asphalt Factory... ...

Aug 21st, 2010
Gas leak in Niles
Several agencies across Michigan responded to a gasoline leak in Niles. It happened around 9 Saturday ...

Aug 21st, 2010
Fire at fertilizer processing facility extinguished
Firefighters extinguished a fire apparently started by spontaneous combustion overnight at the Sand Island Waste ...

Aug 21st, 2010
Update: Fire breaks out at Northeast auto body shop
Close to 20 firefighters responded to a blaze this afternoon at Armando's Body and Paint Shop ...

Aug 20th, 2010
Flowback spill occurs in west Flower Mound
A spill of flowback water occurred at a Williams Exploration drilling site in western Flower ...

Aug 20th, 2010
Texas men critically burned in gas well fire
LUBBOCK (AP) — Two men critically burned in a West Texas oil field accident didn't know ...