DANGERS OF COMBUSTIBLE DUST EXPLOSIONS, OSHA REGULATIONS, AND ANTISTATIC FIBC

Dangers of Combustible Dust by Dr. Paul Holdstock, Texene LLC.

The dangers of combustible dusts have been recognised for many years. Indeed there are long established standards issued by the National Fire Protection Association (NFPA), the Occupational Safety & Health Administration (OSHA) and other national and international bodies that address the issue. However, to date, these standards have in the main been voluntary. Whenever the standards have been implemented, it is clear that dust explosions have been reduced or eliminated, but it is also clear that implementation is not universal. Following three fatal dust explosions in 2003 alone that caused 14 deaths, the US Chemical Safety & Hazard Investigation Board (CSB) launched a wide ranging study of industrial dust explosions. They found that in the period 1980 to 2005 there were 281 dust fires and explosions in US businesses that caused the deaths of 119 people and injured 718 more. A quarter of the explosions occurred at food industry facilities, including sugar plants. Since the study was undertaken there have been a further 70 dust fires and explosions in the US.

The devastating fires and explosions that ripped through the Imperial Sugar refinery in Port Wentworth, GA. on February 7th, killing 13 workers and injuring many more, once again highlighted the dangers created by combustible dust. Sugar is only one of many common materials that can form combustible dusts. Others include flour, feed, plastics, wood, rubber, furniture, textiles, pesticides, pharmaceuticals, dyes, coal, and metals, etc. Many powders stored and transported in bulk bags can form combustible dust clouds when bags are filled or discharged. Powders are normally quite stable in bulk form, but when dispersed as a cloud, or when allowed to build up as a thin layer on surfaces, the combination of the powder and air can form an explosive mixture. All that is then required for an explosion to occur is an ignition source, which could be a naked flame, heating element, frictional spark or an electrostatic discharge.

On April 30th, 2008, The House of Representatives approved the "Worker Protection Against Combustible Dust Explosions and Fires Act of 2008". The Act did not proceed to Senate vote before the end of the 110th Congress and was re-introduced in the 111th Congress on February 4th, 2009 as the "Worker Protection Against Combustible Dust Explosions and Fires Act of 2009". This Act mandates an interim standard for the regulation of combustible dusts to be issued within 90 days of its enactment, to be followed within 18 months by a final standard. The Act defines three essential requirements for the interim standard:

1) Hazard assessment to identify, evaluate, and control combustible dust hazards;
2) A written program that includes provisions for hazardous dust inspection, testing, hot work, ignition control, and housekeeping.
3) Engineering and administrative controls, and operating procedures such as means to control fugitive dust emissions and ignition sources.

The standard mandated by the new Act will place a legal responsibility on businesses to comply with its requirements, some of which will be effective within six months of publication of the interim standard. The requirements necessary to eliminate or mitigate hazards created by combustible dusts are already contained in codes and standards issued by NFPA, and it is likely that these will be implemented as part of the interim and final standard. The principal combustible dust control document is "NFPA 654, Standard for the Prevention of Fires and Explosions from the Manufacturing, Processing, and Handling of Combustible Particulate Solids". NFPA also has commodity-specific combustible dust control standards, including NFPA 61 for agricultural and food processing facilities.

The requirements defined in the new Act echo the main components of the Explosive Atmospheres (ATEX) Directives in Europe. Directive 1999/92/EC, also known as ATEX 137, places a legal responsibility on employers to:
1) Eliminate explosive atmospheres whenever possible;
2) Identify and classify explosive atmospheres that cannot be eliminated;
3) Eliminate all possible ignition sources in areas classified as containing explosive atmospheres; and
4) Implement measures to mitigate any explosion that may occur.

Filling and Discharge Exposure

It is now incumbent upon all companies in the US and Europe to implement effective measures to prevent dust fires and explosions. In some situations, dust clouds are an inevitable part of a process. In such cases, the emphasis is very much on eliminating all possible ignition sources.

Dust clouds are inevitable when filling or emptying FIBC. The dust cloud may be confined to the space inside the bag or may extend outside the bag. Even with pellets and granular materials, dust clouds can be formed from the fines produced when conveying such material. Measures can be taken to mitigate the formation of dust clouds, such as slowing down the filling or emptying process, but as a precaution it is sensible to assume that some fine particulates will be airborne. In order to prevent the explosion of a dust cloud formed from combustible material, it is then necessary to eliminate all possible ignition sources from the areas in which dust clouds are formed, that is within the bag and in the immediate vicinity surrounding the bag. Most ignition sources such as naked flames, heating elements, etc. are easy to identify and eliminate from FIBC handling areas. However, there is one ignition source that may not be quite so obvious but is none the less just as dangerous and requires careful consideration: static electricity.

Static Electricity, are you at Risk?
Static electricity is the ignition source in about 13% of all chemical fires and explosions (Source: Marc Rothschild - Rohm and Haas). Static electricity is generated whenever materials come into contact and rub against each other, particularly when the materials are in particulate form and being moved at significant speeds. Electrostatic charge will readily accumulate on plastics and other insulating materials, which may ultimately result in a spark or brush discharge capable of igniting a flammable atmosphere. In the absence of any measures to control static electricity, there is a real risk that filling or emptying an FIBC will generate enough static electricity to cause and incendiary discharge.

Solutions for Flexible Packaging
There are FIBCs available that do incorporate measures to control static electricity. The US Standard NFPA 654 and the European Code of Practice CLC/TR 50404 permit the use of Type C or Type D FIBC when handling very sensitive combustible powders or where flammable gases or vapours may be present. Type C and Type D FIBC are made like most FIBC from woven polypropylene fabric, but they contain components designed to dissipate static electricity. Type C FIBC contain an interconnected network of conducting yarns that must be grounded in order to dissipate static electricity safely. The need for grounding is the major weakness of Type C. In a detailed investigation of explosion incidents involving FIBC, Dr. Lawrence G. Britton discussed the dangers of using ungrounded Type C FIBC and stated "In particular it should be appreciated that the potential for operator grounding error and sudden nemesis can be very high". The correct use of Type C FIBC will eliminate static electricity as a potential ignition source, but it will require significant capital investment in appropriate fail-safe grounding systems and on-going costs to maintain equipment and train operators. And there is still the risk of human error.

CROHMIQ® Static Protective Type D FIBC
A simpler and better solution to the problem of controlling static electricity is available. CROHMIQ® Static Protective Type D FIBC were the first to provide full control over static electricity without the need for grounding. CROHMIQ® FIBC safely dissipate electrostatic charge safely into the atmosphere via low energy corona discharging. The components used to dissipate charge are an integral part of the woven polypropylene fabric used to construct the FIBC. There is no need to ground CROHMIQ® FIBC and so the need for complex and expensive grounding systems is eliminated, as is the risk of human error. CROHMIQ® FIBC are intrinsically safe and require no input from operators when filling or when emptying.

CROHMIQ® FIBC are designed and engineered to provide total electrostatic safety across a wide range of industries without the need for grounding. This unique static protective technology was pioneered by CROHMIQ's engineers in 1995. Since then, CROHMIQ® FIBC have been used to package over 30 billion pounds of products for the world's most demanding industries, including pharmaceuticals, fine chemicals, pigments, and food products. CROHMIQ® FIBC comply with FDA and EU regulations for food contact applications and meet all the essential safety requirements of national and international standards including IEC 61340-4-4, NFPA 654 and CLC/TR 50404.

CROHMIQ® FIBC are used throughout the world by major companies as an essential part of their regulation of combustible dust hazards. Thanks to their outstanding safety record, CROHMIQ® FIBC are widely acknowledged as the safest and most cost effective solution for controlling static electricity in FIBC handling operations.

For more information about CROHMIQ® FIBC fabrics, visit www.crohmiq.com

Bibliography
Acts of Congress and European Commission Directives
H.R. 5522 - Worker Protection Against Combustible Dust Explosions and Fires Act of 2008.
H.R. 849 - Worker Protection Against Combustible Dust Explosions and Fires Act of 2009.
Directive 1999/92/EC - Minimum requirements for improving the safety and health protection of workers potentially at risk from explosive atmospheres (ATEX 137).

Expert testimony
Testimony of the Honorable William E. Wright, Board Member and Interim Executive U.S. Chemical Safety Board Before the U.S. House of Representatives Committee on Education and Labor, March 12, 2008.
Testimony for the House Education and Labor Committee on H.R. 5522,The Combustible Dust Explosion and Fire Prevention Act of 2008 by Amy Beasley Spencer, Senior Chemical Engineer, National Fire Protection Association, March 12, 2008.

Standards
NFPA 61, Standard for the Prevention of Fires and Dust Explosions in Agricultural and Food Processing Facilities.
NFPA 484, Standard for Combustible Metals.
NFPA 654, Standard for the Prevention of Fires and Dust Explosions from the Manufacturing, Processing, and Handling of Combustible Particulate Solids.
NFPA 655, Standard for Prevention of Sulfur Fires and Explosions.
NFPA 664, Standard for the Prevention of Fires and Explosions in Wood Processing and Woodworking Facilities.
IEC 61340-4-4, Electrostatics - Part 4-4: Standard test methods for specific applications - Electrostatic classification o flexible intermediate bulk containers (FIBC).
CLC/TR 50404, Electrostatics - Code of practice for the avoidance of hazards due to static electricity.

 

TEXENE LLC, Textile Technologies of the 21st Century
Textile Technologies of the 21st Century


TEXENE LLC is a leading manufacturer of technical textiles focused on delivering precision engineered, safety performance products worldwide.

ARTICLES ON ELECTROSTATICS

STATIC HAZARDS USING FLEXIBLE INTERMEDIATE BULK CONTAINERS FOR POWDER HANDLING
In the early 1990's, Dr Laurence G. Britton, a highly respected process safety engineer with Union Carbide Corp. (later Dow Corp.), conducted a study of fire and explosion incidents that occurred when FIBC were ...

DANGERS OF COMBUSTIBLE DUST EXPLOSIONS, OSHA REGULATIONS, AND ANTISTATIC FIBC
Following three fatal dust explosions in 2003 alone, the US Chemical Safety & Hazard Investigation Board (CSB) launched a wide ranging study of industrial dust explosions.  This first issue of our Electrostatic Safety ...

CHOOSING SAFE STATIC CONTROL FIBC
The second issue of our Electrostatic Safety Review outlines the development of conductive Type C FIBC and the later development of CROHMIQ, the world's first truly effective Type D FIBC fabric, which provides ...

TESTING & CERTIFYING THE SAFETY OF STATIC PROTECTIVE FIBC
The third issue in our series of Electrostatic Safety Reviews describes the rigorous testing that is demanded by national and international standards such (IEC, CENELEC, NFPA, etc.) in order to prove the safety of ...

NEW DEVELOPMENTS IN SAFETY STANDARDS FOR STATIC PROTECTIVE FIBC
Companies that handle combustible powders in bulk bags, or empty products from bulk bags in environments where flammable solvents may be present rely on safe antistatic FIBC to prevent fires and explosions. Proving safety ...

CHEMICAL ACCIDENTS IN THE NEWS

Jul 28th, 2010
Frontier Refinery Fire Under Control
Around 5:40 this morning, a fire broke out in the crude unit of the Frontier Oil ...

Jul 28th, 2010
Fire fought at recycling plant near Sarasota-Bradenton International Airport
SARASOTA COUNTY - It took firefighters about two hours Tuesday to put out a fire ...

Jul 27th, 2010
Explosion leads to chemical spill
An explosion led to a hazardous chemical spill Tuesday night on the Eastside. Capt. Rita ...

Jul 26th, 2010
Fumes Force Evacuation of Southwestside Business
Diesel fumes, reportedly, forced an evacuation of a business called Aspen Systems in the 5100 block ...

Jul 26th, 2010
Two Die in Pittsburgh-area Well Explosion
An oil storage tank at a natural gas well exploded Friday morning, killing two workers, ...

Jul 23rd, 2010
2 Killed In Pittsburgh Gas Well Explosion
Resulting Fire Spewed Black Smoke For... ...

Jul 22nd, 2010
Potter zinc plant explosion claims 2
An investigation has begun to determine the cause of an explosion at a Beaver County ...

Jul 19th, 2010
1 hospitalized after Morristown plant explosion
According to the Citizen Tribune, toluene liquid, often used as a solvent, boiled into a ...

Jul 19th, 2010
Three injured in Adams County blast
BENDERSVILLE, Monday, July 19, 2010 -- Two men and a child were burned Sunday in an explosion ...

Jul 18th, 2010
Officials investigating Santa Clara recycling fire
SAN JOSE, Calif. (AP) - Santa Clara fire officials are investigating a fire at a ...

Jul 18th, 2010
Oil Fire Quickly Tamed At Local Refinery
WHITEHALL, Ohio -- The Heartland Oil Refinery on East 5th Avenue was the scene of ...

Jul 18th, 2010
Electrical problem sparks fire at paper plant
RIEGELWOOD, N.C. -- Officials say an electrical problem is to blame for a fire ...

Jul 17th, 2010
No one injured in blaze at paint warehouse
A Tomball paint warehouse remains on fire 12 hours after the five-alarm blaze was reported this ...

Jul 17th, 2010
Explosion, fire rock Independence corncob processor
INDEPENDENCE, Iowa (AP) — An apparent dust explosion at a corn cob processing plant in Independence ...

Jul 14th, 2010
At Least 14 Hurt In Pennsylvania Steel Plant Blast
At least 14 people were hurt on Wednesday in a blast at a U.S. Steel ...

Jul 13th, 2010
Ammonia leak clears Coors plant
GOLDEN — An ammonia leak at the Molson Coors Brewing Co. sent two workers to the ...

Jul 12th, 2010
Fire damages factory in Bridgeport
BRIDGEPORT — Heavy smoke and flames engulfed portions of the C.J. Robinson Specialty Wax Company ...

Jul 12th, 2010
Chemical leak forces Farmington evacuations
FARMINGTON, N.M.—About 20 people were forced to evacuate their homes in Farmington on Sunday ...

Jul 11th, 2010
Cause of explosion unknown: One man seriously injured and reportedly in area burn unit [Laurel Leader-Call, Miss.]
July 11--VOSSBURG -- Clarke County Sheriff Todd Kemp and other emergency personnel responding to Friday's ...

Jul 10th, 2010
Minor Explosion in Lafayette
Firefighters and ambulance rushed to a local health and beauty plant after a scare Saturday ...

Jul 9th, 2010
Welder critically injured in work site blast
ENGLEWOOD, COLO. — A welder working in Englewood has been critically injured after vapors inside a ...

Jul 8th, 2010
Ville Platte Man Injured In Hazardous Material Spill
This morning at 10:42 a.m., State Police received a telephone call advising of an incident ...

Jul 6th, 2010
6 fire departments fight Uniroyal blaze near Madison
STOUGHTON, Wis. (AP) - Firefighters from six departments battled a blaze at Uniroyal Engineered Products ...

Jul 6th, 2010
Three sent to hospital after explosion at York business
YORK, Maine — Three people were sent to the hospital Saturday after an explosion at a ...

Jul 5th, 2010
Acid Spill Evacuated Downtown Jewelers Exchange
SAN DIEGO - Fumes from a spilled gallon container of muriatic acid sent a 60-year-old ...

Jul 2nd, 2010
Workers in walkout over fatal blast at refinery
A 24-year-old man from Grimsby died in the explosion at the Lindsey Oil Refinery (LOR), ...